Tata Communications Data Center Ambattur

Tata Communications Data Center Ambattur Site Specs and Electrical Specs



Site Specs

Each floor plate - 40,000 sq. ft. per floor
Planned data center build - 200,000 sq. ft. (data center space)
Total building space - 280,000 sq. ft.
Floor loading capacity - 1500 Kg/sq m
Slab to slab height - 5.0 meters
Clear height - 3.6 meters
False floor - 800 mm
Rack space - 1,200 standard racks per floor and a total of four floors
Rack power - 6 KVA average power per rack


Electrical Specs

110 KV substation

5000 KVA power
Day 1 and scalable up to 30,000 KVA

Transformers
4 x 2500 KVA in Phase 1 and 7 x 2500 KVA final phase of the expansion working in N+1 mode

DG
2 X 2500 KVA in Phase 1 and scale up in terms of N+1 in the final phase of expansion to cater 30,000 KVA power for the building

Service lift
Loading capacity 3000 Kg, 3.3 M x 2.4 M x 2.0 M (D x H x W)

Passenger lift – 2 No

Chillers
3 x 1050 TR in Phase 1 and expanded up to 7 x 1050 TR as ultimate capacity for N+1 configuration



Network and Local Carriers

• Dual fi ber duct available from road to building
• Fiber available along the main road from local carriers, the same to be extended to MMR area, proposed at the ground fl oor of the building
• MAN network available from Tata Communications in dual ring architecture
• Fiber network available from Tata Tele
• Dual diverse data duct available from MMR to each data center server hall